4-72 
 
11 Performance Control Functions 
 
11- 00  Prevention of Reverse operation 
Range 
 
【0】:Reverse command is enabled   
【1】:Reverse command is disabled 
  11-00=1, the reverse command is disabled. 
11- 01  Carrier Frequency 
Range 
【1~16】kHz 
  While IGBT-driven inverter can provide low-noise working environment, the high frequency devices 
have carrier frequency waveform cutting, it may interfere with external electronic device, even caused 
vibration when connected with motor, and then need to adjust the carrier frequency. 
11- 02 
Carrier mode selection 
Range 
 
【0】:Carrier mode0      3-phase PW M modulation 
【1】:Carrier mode1      2-phase PW M modulation 
【2】:Carrier mode2   Soft PWM modulation 
  Mode 0: 3-phase PWM Modulation Three Output transistors on at the same time (Full Duty). 
  Mode 1: 2-phase PWM Modulation Two output transistors on at the same time (2/3 Duty). 
  Mode 2: Random PWM Modulation This modulation method will use 3-phase PWM and 2-phase 
PWM modulation in a random mode. 
 
Modes  Name  IGBT Duty 
Heat 
Losses
Torque 
Performance
Waveform 
Distortion 
Motor 
Noise 
0 3-Phase PWM  100%  High  High  Low  Low 
1 2-Phase PWM  66.6%  Low  Low  High  High 
2  Soft PWM 
Between mode0 & 
mode1 
Medium Medium Medium Medium 
 
11- 03  Carrier Frequency Reduction by temperature rise 
Range 
【0】:Disable    
【1】:Enable 
  When inverter (heat sink) temperature rises above 80°C the Carrier Frequency is reduced by 4K. 
  When the temperature falls below less than 70°C,Carrier Frequency is reset to default.   
  Temperature can be displayed by setting parameter 12-00=04000.   
70℃
80℃
t1
t2
T0
Temperature
Carrier 
Frequency
10K
4K
t1
t2
T0