  The fire Mode function is activated by using one of the external multifunction inputs S1 to S6 and 
setting the relevant parameter for the selected input by 03-00~03-05 =【28】 
  Fire mode can also be enabled by setting the functions of S1 to S6 by communication method. 
 
  Once Fire Mode is activated following takes place:-   
 
1. The operator panel indicates FIrE, and the FIrE will be recorded in inverter fault log. 
2. The inverter will run at full speed up to the maximum of inverter running frequency as set in 00-12, 
unless the main power is lost or cut off or the inverter itself breaks down. 
3. When Fire Mode is activated, all protectional functions and alarms, such as ES, BB, OV, OC etc, will 
be ignored. STOP key on the operator panel becomes ineffective. 
4. To reset fire mode: turn power off, remove fire mode input signal, and power on. 
 
03- 06  Up/Down Frequency Step 
Range 
【0.00~5.00】Hz 
Example: S1: 03- 00=【8】Up frequency command, S2: 03- 01=【9】Down frequency command, 
03- 06=【
△】Hz  
 
 
Mode1: UP or DOWN input terminals are turned on for less than 2 sec, for every On operation frequency 
△
changes by   Hz. 
S1
S2
ON ON ON
Hz
T
△Hz
Actual output 
frequency
ON ON ON
 
Mode 2: If UP or DOWN input terminals are turned on for more than 2 sec,the original UP/DOWN mode is 
restored output frequency ramps up or down as long as the input is kept ON. 
S1
S2
ON
≥2Sec
OFF
OFF
ON
≥2Sec
T
Maximum 
output 
frequency
△H1
t1
△H2
t2