4-76
appropriate. Motor synchronous speed = 120 x Rated frequency/Number of poles.
12- 04 Custom Units (Line Speed) Display Mode
Range
【0】:Drive Output Frequency is Displayed
【1】:Line Speed is Displayed in Integer (xxxxx)
【2】:Line Speed is Displayed with One Decimal Place (xxxx.x)
【3】:Line Speed is Displayed with Two Decimal Places (xxx.xx)
【4】:Line Speed is Displayed with Three Decimal Places (xx.xxx)
12- 04≠0,line speed is displayed while the inverter is running or stopped.
12- 05 Inputs and output Logic status display (S1 to S6) & RY1~2
Range
Read only(Panel read only)
When any of S1 ~ S6 is turned on, corresponding segments on the digital display digits will be on.
When relay output RY1/RY2 are on, the corresponding digit will be on as shown below.
Example 1: The following figure shows 12 - 05 display status,
when S1, S3, S5,S6 Inputs are ON and S2, S4, RY1 and RY2 are OFF.
S1 S2 S3 S4 S5 S6
Example 2: The following figure shows 12 - 05 display status
when S2, S3, S4 inputs are ON and S1, S5,S 6 are OFF but RY1, RY2, PLC are ON.
RY1
RY2
PLC
12- 06 Alarm Selections for Inverter Components Life Expectancy
Range
xxxx0: life alarm of inrush current suppression circuit is invalid
xxxx1: life alarm of inrush current suppression circuit is valid
xxx0x: life alarm of control circuit capacitors is invalid
xxx1x: life alarm of control circuit capacitors is valid
xx0xx: life alarm of main circuit capacitors is invalid
xx1xx: life alarm of main circuit capacitors is valid
Example:set 12- 06=00111,if inrush current suppression circuit or control circuit capacitors or main circuit
capacitors is damaged,display LIFE1,LIFE2,LIFE3 respectively. Alerts the user that inverter needs repair
12- 08 Display of inrush current suppression circuit
Range 0~100
For every 1000 power on cycle, the percentage value will reduce by 1%. When this becomes lower
than 30%, inverter displays "Life1".
12- 09 Display of control circuit capacitors
Range 0~100
For every 80-hour operation, the percentage value will reduce by 1%. When this becomes lower than
5%, inverter displays "Life2".
12- 11 Output current when Fault appeared
Range ----
12- 12 Output voltage when fault appeared
Range ----
12- 13 Output frequency when fault appeared
Range ----
12- 14 DC bus voltage when fault appeared