can not be the same. Otherwise the panel will display Err2.
00- 07 Main and Alternative Frequency Command Modes
Range
【0】: Main or Alternative Frequency.
【1】: Main Frequency + Alternative Frequency
When 00 - 07 =【0】, the frequency source is set by the Main frequency parameter 00-05 ( Default) or
by the Alternative frequency parameter 00-06.
Use any of the external terminals S1 to S6 and set the relevant parameter 03-00 to 03-05 =【13】to
switch from Main to Alternative source..
When 00 - 07 =【1】, The frequency command will be the result of setting of main and alternative
frequencies.
00- 08 Communication Frequency Command
Range
【0.00~599.00】Hz
This parameter can be used to read the set frequency in communication mode
This parameter is only effective in the communication mode.
00- 09 Frequency Command save on power down (Communication mode)
Range
【0】: Disable
【1】: Enable
00-09=【0】 Keypad frequency is saved.
00-09=【1】 Frequency set by communication is saved.
00-10 Initial Frequency Selection
Range
【0】:By Current Freq Command
【1】:By Zero Freq Command
【2】:By 00-11
00-11 Initial Frequency Setpoint
Range
【0.00~599.00】Hz
This parameter is only effective in keypad mode
When 00-10=【0】,the initial frequency will be current frequency.
When 00-10=【1】,the initial frequency will be 0.
When 00-10=【2】,the initial frequency will be as set by parameter 00-11..
00-12 Frequency Upper limit
Range
【0.01~599.00】Hz
00-13 Frequency Lower limit
Range
【0.00~598.99】Hz
When 00-13 and the command frequency are both set to 0.00, if RUN is pressed ” Stpo” is displayed.
When Frequency command is higher than preset in 00-13 inverter output will ramp up from 0.00 to the
command frequency.
When 00-13> 0, and the frequency command value ≤ 00-13, inverter output will ramp up from preset
in lower limit to the command frequency.
Frequency
Upper Limit
Frequency
Lower limit
0
Hz
T