5-13
5.4 Routine and periodic inspection
To ensure stable and safe operation, check and maintain the inverter at regular intervals.
Use the checklist below to carry out inspection.
Disconnect power after approximately 5 minutes to make sure no voltage is present on the output
terminals before any inspection or maintenance.
Items Details
Checking
period
Methods Criteria Remedies
Daily 1Year
Environment & Ground connection
Ambient
conditions at
the installation
Confirm the
temperature and
humidity at the machine
Measure with
thermometer
and hygrometer
Temperature:
-10 – 40oC
(14-120 )
Humidity:
Below
95%RH
Improve the
ambient or
relocate the
drive to a
better area.
Are there inflammable
materials in the
vicinity?
Visual check
Keep area
clear
Installation
Grounding
Any unusual vibration
from the machine
Visual, hearing
check
Keep area
clear
Secure
screws
Is the grounding
resistance correct?
Measure the
resistance with
a multi-tester
200Vclass:
below 100
Improve the
grounding if
needed.
Terminals & Wiring
Connection
terminals
Any loose parts or
terminals?
Visual check
Check with a
screwdriver
Correct
installation
requirement
Secure
terminals and
remove rust
Any damage to the
base ?
Any corroded
Terminals?
Wiring
Any broken wires?
Visual check
Correct
wiring
requirement
Rectify as
necessary
Any damage to the wire
insulation?
Voltage
Input power
voltage
Is the voltage of the
main circuit correct?
Measure the
voltage with a
multi-tester
Voltage must
conform with
the spec.
Improve input
voltage if
necessary.
Circuit boards and components
Printed circuit
board
Any contamination or
damage to printed
circuit board?
Visual check
Correct
component
condition
Clean or
replace the
circuit board
Discolored, overheated,
or burned parts
Capacitor
Any unusual odor or
leakage
Replace
capacitor or
inverter
Any physical damage
or protrusion
Power
component
Any dust or debris
Clean
components
Check resistance
between each terminals
Measure with a
multi-tester
No short
circuit or
broken circuit
in
three-phase
output
Consult with
the supplier