4-10 
 
Gro up 01- V/F Pattern selection & Setup 
No. Description  Range 
Factory 
Setting 
Unit Note
01-00 
Volts/Hz Patterns  0~18  0/9  -   
01-01 
V/F Max voltage 
200V:170.0~264.0 
400V:323.0~528.0 
220.0/440.0 Vac  
01-02 
Base Frequency  0.20 ~ 599.00 50.00/60.00 Hz  
01-03 
Max Frequency Voltage Ratio  0.0 ~ 100.0  100.0  %   
01-04 
Mid Frequency 2  0.10 ~ 599.00 25.00/30.00 Hz  
01-05 
Mid Frequency Voltage Ratio 2  0.0 ~ 100.0  50.0  %   
01-06 
Mid Frequency 1  0.10 ~ 599.00 10.00/12.00 Hz  
01-07 
Mid Frequency Voltage Ratio 1  0.0 ~ 100.0  20.0  %   
01-08 
Min Frequency  0.10 ~ 599.00 0.50/0.60 Hz  
01-09 
Min Frequency Voltage Ratio  0.0 ~ 100.0  1.0  %   
01-10 
Volts/Hz Curve Modification 
(Torque Boost)   
0 ~ 10.0  0.0  %  *1 
01-11 
V/F start Frequency  0.00~10.00 0.00 Hz  
01-12 
Slip compensation gain 
0.05~10.00 0.10 S  
01-13 
V/F Mode Select  0 : Mode 0    1 : Mode 1  by models 
-  *7 
 
 
Gr o up 02- Motor parameters 
No. Description  Range 
Factory 
Setting 
Unit Note
02-00 
Motor No Load Current  0~[(Patameter 02-01)-0.1] 
- Amps(AC) *3 
02-01 
Motor Rated Current (OL1)  0.2~100  -  A  *3 
02-02 
Motor rated Slip 
Compensation  
0.0 ~ 200.0  0.0  %  *1 
02-03 
Motor rated speed  0~39000 
- 
Rpm *3 
02-04 
Motor rated voltage 
200V: 170.0~264.0            
400V: 323.0~528.0 
220.0/440.0 V 
 
02-05 
Motor rated power  0.1~37.0  -  KW 
 
02-06 
Motor rated frequency  0~599.0  50.0/60.0 Hz 
 
02-07 
Motor pole number 
2 ~16  4 
- 
 
02-08 
~   
02-13 
Reserved 
02-14 
Auto Tune 
0: Disable 
0   
1: Start Auto tune function. 
02-15 
Stator resistance gain 
----   
*3*4
02-16 
Rotor resistance gain 
----   
*3*4