Appendix-1 Instructions for UL
Recommended Input Fuse Selection
Drive Model E510
Fuse Type
Manufacturer: Bussmann / FERRAZ SHAWMUT
Model Fuse Ampere Rating (A)
200 V Class Single / Three-Phase Drives
2P5-HXXX Bussmann 20CT 690V 20A
201-HXXX Bussmann 20CT 690V 20A
202-HXXX Bussmann 35FE 690V 35A
203-HXXX Bussmann 50FE 690V 50A
2P5-H3XX Bussmann 20CT 690V 20A
201-H3XX Bussmann 20CT 690V 20A
202-H3XX Bussmann 20CT 690V 20A
203-H3XX Bussmann 30FE 690V 30A
205-XXXX Bussmann 50FE 690V 50A
208-XXXX Bussmann 63FE 690V 63A
210-XXXX FERRAZ SHAWMUT A50QS100-4 500V 100A
215-XXXX Bussmann 120FEE / FERRAZ A50QS150-4 690V 120A / 500V 150A
220-XXXX FERRAZ SHAWMUT A50QS150-4 500V 150A
SICP_C710616_28B_1_0.book Page 551 Wednesday, May 13, 2009 4:50 PM
400 V Class Three-Phase Drives
401-XXXX Bussmann 10CT 690V 10A
402-XXXX Bussmann 16CT 690V 16A
403-XXXX Bussmann 16CT 690V 16A
405-XXXX Bussmann 25ET 690V 25A
408-XXXX Bussmann 40FE 690V 40A
410-XXXX Bussmann 50FE 690V 50A
415-XXXX Bussmann 63FE 690V 63A
420-XXXX Bussmann 80FE 690V 80A
425-XXXX FERRAZ SHAWMUT A50QS100-4 500V 100A
Drive Model E510
Fuse Type
Model Fuse Ampere Rating (A)
Motor Overtemperature Protection
Motor overtemperature protection shall be provided in the end use application.
Field Wiring Terminals
All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that are to be
made to each terminal and indicate that copper conductors, rated 75°C are to be used.
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will not rise above
value. Please see electrical ratings for maximum voltage and table below for current.
The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-circuit tolerance of the
power supply being used.
Suitable for use on a circuit capable of delivering not more than ( A ) RMS symmetrical amperes for ( Hp ) Hp in 240 / 480 V class drives motor
overload protection.
Horse Power ( Hp ) Current ( A )
1 - 50 5,000
Voltage ( V )
240 / 480
Manufacturer: Bussmann / FERRAZ SHAWMUT