4-20
Group 08- Drive & Motor Protection Functions
No. Description Range
Factory
Setting
Unit Note
08-00
Trip Prevention
Selection
xxxx0: Enable Trip Prevention During
Acceleration
xxxx1: Disable Trip Prevention During
Acceleration
xxx0x: Enable Trip Prevention During
Deceleration
xxx1x: Disable Trip Prevention During
Deceleration
xx0xx: Enable Trip Prevention in Run
Mode
xx1xx: Disable Trip Prevention in Run
Mode
x0xxx: Enable Over Voltage Prevention
in Run Mode
x1xxx: Disable Over Voltage Prevention
in Run Mode
01000 - *5
08-01
Trip Prevention Level
During Acceleration (%)
50 ~ 200 200
%
1
08-02
Trip Prevention Level
During Deceleration (%)
50 ~ 200 200
08-03
Trip Prevention Level in
Run Mode (%)
50 ~ 200 200
08-04
Over Voltage
Prevention
Level in Run Mode
350.0~390.0/700.0~780.0
380.0/7
60.0
VD
C
08-05
Electronic Motor
Overload Protection
Operation Mode
0: Disable
1: Enable
1 - *7
08-06
Operation After
Overload Protection is
Activated
0: Coast-to-Stop After Overload Protection is
Activated
1: Drive Will Not Trip when Overload Protection
is Activated (OL1)
0 -
08-07
Over Heat Protection
( cooling fan control)
0: Auto (Depends on temp.)
1: Operate while in RUN Mode
2: Always Run
3: Disabled
1 -
08-08
AVR Function
(Auto Voltage
Regulation)
0: AVR Function is enabled
4 - *5
1: AVR Function is disabled
2: AVR Function is disabled for Stop
3: AVR Function is disabled for Deceleration.
4: AVR Function is disabled for Stop and
Deceleration.
5: When VDC>360V, AVR Function is disabled
for Stop and Deceleration.
08-09
Input Phase Loss
Protection
0: Disable
1: Enable
0 -
08-10
Output Phase Losts
Protection
0: Disable
0 -
1: Enable
08-11
Motor Type Selection
0: Overload protection (Standard Motor)
0 -
1: Overload protection (Inverter Duty Motor)
08-12
Motor Overload
Protection Curve
0: Motor Overload Protection for General loads
(OL=103 %) (150% for 1 Minutes)
0 -
1: Motor Over load Protection for HVAC (Fan &
Pump) (OL=113%) (123% for 1 Minutes).
1
Base on the percentage of inverter rated current.