*1
Group 06- Auto Run Function (Auto Sequencer)
No. Description Range
Factory
Setting
Unit Note
06-00
Auto Run Mode
Selection
(Sequencer)
0: Disabled.
1: Single cycle.
(Continues to run from the Unfinished step if
restarted).
2: Periodic cycle.
(Continues to run from the unfinished step if
restarted).
3: Single cycle, then holds the speed Of final
step to run. (Continues to run from the
unfinished step if restarted).
4: Single cycle.
(Starts a new cycle if restarted).
5: Periodic cycle.
(Starts a new cycle if restarted).
6: Single cycle, then hold the speed of final step
to run. (Starts a new cycle if restarted).
0 -
06-01
Auto _ Run Mode
Frequency Command 1
0.00~599.00
0.00 Hz *1
06-02
Auto _ Run Mode
Frequency Command 2
0.00 Hz *1
06-03
Auto _ Run Mode
Frequency Command 3
0.00 Hz *1
06-04
Auto _ Run Mode
Frequency Command 4
0.00 Hz *1
06-05
Auto _ Run Mode
Frequency Command 5
0.00 Hz *1