EasyManua.ls Logo

TECO e510 series - Inspection & Maintenance Functions

TECO e510 series
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-25
Group 12 Digital Display & Monitor Functions
No. Description Range
Factory
Setting
Unit Note
12-07
Detect Main Circuit
Capacitors
Reserved
12-08
Display of Inrush Current
Suppression Circuit
0~100 100 %
12-09
Display of Control Circuit
Capacitors
0~100 100 %
12-10
Reserved
12-11
Output Current when
Fault Appeared
---- 0 A
12-12
Output Voltage when
Fault Appeared
---- 0 Vac
12-13
Output Frequency when
Fault Appeared
---- 0 Hz
12-14
DC Bus Voltage when
Fault Appeared
---- 0 Vac
12-15
Frequency Command when
Fault Appeared
---- 0 Hz
Group 13 Inspection & Maintenance Functions
No. Description Range
Factory
Setting
unit Note
13-00
Drive Horsepower Code ---- - - *3
13-01
Software Version ---- - - *3*4
13-02
Fault Log (Latest 3
Faults)
---- - - *3*4
13-03
Accumulated Inverter
Operation Time 1
0~23 - hour *3
13-04
Accumulated Inverter
Operation Time 2
0~65535 ---- day *3
13-05
Accumulated Inverter
Operation Time Mode
0: Power On time
1: Operation time
0 - *3
13-06
Parameter Lock
0:Enable all Functions
1:Preset Speeds from 05-01 to 05-15 Can’t be
Changed
2:All Functions Can’t be Changed Except
for Preset speeds from 05-01 to 05-15
3:Disable All Functions Except 13-06
0 -
13-07
Parameter Lock Code 00000~65535 00000 -
13-08
Reset Drive to Factory
Settings
1150: Reset to factory setting. 50Hz,220V/380V
system.
1160: Reset to factory setting. 60Hz,220V/380V
system.
1250: Reset to factory setting 50Hz,230V/400V
system.
1260: Reset to factory setting 60Hz,230V/460V
system.
1350: Reset to factory setting 50Hz,220V/415V
system.
1360: Reset to factory setting 60Hz,230V/400V
system.
1112: Reset PLC
00000 -

Table of Contents