RUN 
command
03-11=14
Hz
T
ON
OFF
RUN STOP
 
 
03- 19  Relay Output Status Type 
Range 
 
【0】:A (Normally open) 
【1】:B (Normally close) 
 When 03-19=0, 
  When the set conditions of 03-11,03-12 are met , relay contact is closed, otherwise it will be open.. 
 When 03-19=1, 
  When the set conditions of 03-11,03-12 are met ,relay contact will open,Otherwise it will be closed. 
 
03- 20  Internal / External Multi-Function Input Terminal Selection 
Range 
【0~63】 
03- 21  Action to Set the Internal Multi-Function Input Terminals 
Range 
【0~63】 
 
 
Parameter 03-20 determines if external/ internal control for multi-function inputs S1-S6 is selected.   
The corresponding contact is set to 1 when internal multi-tunction input is selected and it is set to 0 
when the external one is selected.   
  The input selection is according to the decimal value set.   
 
DI  S6 S5 S4 S3 S2 S1 
Binary  
5
2  
4
2  
3
2  
2
2  
1
2  
0
2  
Decimal   32 16 8 4 2 1