Gr o up 00- Basic parameters 
No. Description  Range 
Factory 
Setting 
Unit Note
00-00 
Control Mode Selection 
0:V/F Mode 
0 
- 
 
1:Vector Mode 
00-01 
Reserved 
00-02 
Main Run Command 
Source Selection 
0:Keypad 
0 -  
1:External Run/Stop Control 
2:Communication 
3:PLC 
00-03 
Alternative Run Command   
Source Selection 
0:Keypad 
0 -  
1:External Run/Stop Control 
2:Communication 
00-04 
Operation Modes for 
External Terminals 
0:Forward/Stop-Reverse/Stop 
0 -  
1:Run/Stop- Reverse/Forward 
2: 3 Wire Control Mode-Run/Stop 
00-05 
Main Frequency Command 
Source Selection 
0:UP/DOWM of Keypad 
0 - 
 
1:Potentiometer on Keypad   
2:External AI1 Analog Signal Input   
3:External AI2 Analog Signal Input   
4:External Up/Down Frequency Control  
5:Communication Setting Frequency   
6:PID Ouput Frequency   
7:Pulse Input 
*6 
00-06 
Alternative Frequency 
Command Source Selection 
0:UP/DOWM of Keypad 
4 - 
 
1:Potentiometer on Keypad   
2:External AI1 Analog Signal Input   
3:External AI2 Analog Signal Input   
4:External Up/Down Frequency Control  
5:Communication Setting Frequency   
6:PID Ouput Frequency   
7:Pulse Input 
*6 
00-07 
Main and Alternative 
Frequency Command Modes 
0:Main or Alternative Frequency 
1:Main Frequency+ Alternative 
 Frequency 
0 -  
00-08 
Communication 
Frequency Command 
0.00~599.00 0.00 Hz *4 
00-09 
Frequency Command 
Save on Power Down 
0: Disable 
0 -  
1: Enable 
00-10 
Initial Frequency 
Selection (keypad mode) 
 
0:by Current Frequency Command 
0 -  
1:by 0 Frequency Command 
2:by 00-11 
00-11 
Initial Frequency Setpoint 
0.00~599.00