4-73
11- 04 S-Curve Acc 1
11- 05 S-Curve Acc 2
11- 06 S-Curve Dec 3
11- 07 S-Curve Dec 4
Range
【0.0 ~ 4.0】Sec
Use S Curve parameters where a smooth acceleration or deceleration action is required, this will
prevent possible damage to driven machines by sudden acceleration/deceleration.
S1
S2
S3
S4
RUN
command
Actual
output
frequency
RUN
T
※ Note:
Regardless of the stall prevention period, actual acceleration and deceleration time =preset
acceleration / deceleration time + S curve time.
Please set the required individual S curve times in the parameters (11-04~11-07)
When S curve time (11-04~11-07) is set as 0, the S curve function is disabled.
The calculation of S curve time is based on the Maximum output frequency of motor (01-02), Please
refer to the parameter (00-14/00-15/00-16/00-17).
11- 08 Skip frequency 1
11- 09 Skip frequency 2
11-10 Skip frequency 3
Range
【0.00 ~ 599.00】Hz
11-11 Skip frequency range (±frequency band)
Range
【0.00 ~ 30.00】Hz
Skip frequency parameters can be used to avoid mechanical resonance in certain applications.
Example:11-08=10.00(Hz); 11-09=20.00(Hz); 11-10=30.00(Hz); 11-11=2.00(Hz).
10Hz ±2Hz=8~12Hz
20Hz ±2Hz=18~22Hz Skip frequency
30Hz ±2Hz=28~32Hz
11- 12 V/F Energy Saving Gain (VF)
Range
【0 ~ 100】%
11- 13 Regeneration Prevention Function
Range
【0】: Regeneration prevention function is disabled
【1】: Regeneration prevention function is enabled
【2】: Regeneration prevention function is enabled only during constant speed
Regeneration Prevention Function:
During excessive energy regeneration, the Vpn (DC bus) voltage will Increase and lead to
11-11
11-10
11-09
11-08