4-30
00-14 Acceleration Time 1
Range
0.1~3600.0 s
00-15 Deceleration Time 1
Range
0.1~3600.0 s
00-16 Acceleration Time 2
Range
0.1~3600.0 s
00-17 Deceleration Time 2
Range
0.1~3600.0 s
Preset Acceleration and Deceleration times set by above parameters are the time taken for the output
frequency to ramp up or ramp down between the Upper and the lower frequency limits.
When 01- 00=18, Base frequency= the setting value of parameter 01-02;
When 01- 0018, Base frequency =50.00 (or 60.00)
Actual acceleration and deceleration time is calculated as follows
(00-15)x(set frequency-the minimum starting frequency)
Actual acceleration time=
(00-14)x(set frequency-the minimum starting frequency)
Base frequency
Actual deceleration time=
Base frequency
Base Frequency
Set frequency
Acc-time
00-14
Dec-time
00-15
Actual acc-time
Actual dec-time
Hz
T0
The minimum
starting
frequency
00-18 Jog Frequency
Range
0.00~599.00Hz
00-19 Jog Acceleration Time
Range
0.1~3600.0Sec
00-20 Jog Deceleration Time
Range
0.1~3600.0Sec
The JOG function is operational by using the multi-function input terminals S1 to S6 and setting the
relevant parameters 03-00~03-05 to 6JOG FWD or7JOG REV. Refer to parameter group 3.