11- 14  Regeneration Prevention Voltage Level 
Range 
【200V:300.0~400.0, 400V: 600.0~800.0】V 
  Regeneration prevention voltage level:    if the DC bus voltage level is set too low, then over-voltage 
protection will not be reached, but the actual deceleration time will be extended. 
11- 15  Regeneration Prevention Frequency Limit 
Range 
【
0.00
~
15.00Hz
】
 
  Sets the regeneration prevention frequency limit. 
11- 16  Regeneration Prevention Voltage Gain 
Range 
【0~200】 
 
11- 17  Regeneration Prevention Frequency Gain 
Range 
【
0~200
】
 
 Regeneration avoidance function response can be improved by increasing 11-16/11-17. This will 
improve the response to voltage changes on the DC bus, but may cause output frequency 
instability.Set 11-16 as low as possible to reduce output frequency instability if this does not correct 
the instability then reduce the setting of parameter 11-17. 
  Set 11-16 as low as possible to reduce the output frequency instability. If this does not correct the 
instability then reduce the setting of parameter 11-17, and re-adjust 11-16. 
 
12 Monitor Function Group 
 
12- 00  Display Mode 
Range 
 
 
 
 
 
 
 
 
 
 
0     0   0   0      0 
MSD LSD 
00000~88888      Each digit can be set from 0 to 8 as listed below. 
【0】:Disable display(frequency& parameters) 
【1】:output Current 
【2】:output Voltage 
【3】:DC voltage 
【4】:Temperature 
【5】:PID feedback 
【6】:AI1 
【7】:AI2 
【8】:Count Status 
  MSD= Most significant digit. LSD= Least significant digit. 
Note: MSD of parameter 12-00 sets the power on display; other digits set user selected displays.   
 
12- 01  PID Feedback Display format 
Range 
 
 
【0】:Displayed in Integer (xxx) 
【1】:One Decimal Place (xx.x) 
【2】:Two Decimal Places (x.xx) 
12- 02  PID Feedback Display Unit Setting 
Range 
 
 
【0】:xxx-- 
【1】:xxxpb(pressure) 
【2】:xxxfl(flow) 
 
12- 03  Custom Units (Line Speed) Display Mode 
Range 
【0~65535】Rpm 
  Set motor rated RPM in this parameter if required then the display will show this value when inverter 
output frequency reaches the motor name plate frequency. 50Hz or 60 Hz as appropriate. 
  The line speed display is linearly proportional to the output frequency 0 to 50Hz or 0-60 Hz as