4-75
11- 14 Regeneration Prevention Voltage Level
Range
200V:300.0~400.0, 400V: 600.0~800.0V
Regeneration prevention voltage level: if the DC bus voltage level is set too low, then over-voltage
protection will not be reached, but the actual deceleration time will be extended.
11- 15 Regeneration Prevention Frequency Limit
Range
0.00
15.00Hz
Sets the regeneration prevention frequency limit.
11- 16 Regeneration Prevention Voltage Gain
Range
0~200
11- 17 Regeneration Prevention Frequency Gain
Range
0~200
Regeneration avoidance function response can be improved by increasing 11-16/11-17. This will
improve the response to voltage changes on the DC bus, but may cause output frequency
instability.Set 11-16 as low as possible to reduce output frequency instability if this does not correct
the instability then reduce the setting of parameter 11-17.
Set 11-16 as low as possible to reduce the output frequency instability. If this does not correct the
instability then reduce the setting of parameter 11-17, and re-adjust 11-16.
12 Monitor Function Group
12- 00 Display Mode
Range
0 0 0 0 0
MSD LSD
00000~88888 Each digit can be set from 0 to 8 as listed below.
0:Disable display(frequency& parameters)
1:output Current
2:output Voltage
3:DC voltage
4:Temperature
5:PID feedback
6:AI1
7:AI2
8:Count Status
MSD= Most significant digit. LSD= Least significant digit.
Note: MSD of parameter 12-00 sets the power on display; other digits set user selected displays.
12- 01 PID Feedback Display format
Range
0:Displayed in Integer (xxx)
1:One Decimal Place (xx.x)
2:Two Decimal Places (x.xx)
12- 02 PID Feedback Display Unit Setting
Range
0:xxx--
1:xxxpb(pressure)
2:xxxfl(flow)
12- 03 Custom Units (Line Speed) Display Mode
Range
0~65535Rpm
Set motor rated RPM in this parameter if required then the display will show this value when inverter
output frequency reaches the motor name plate frequency. 50Hz or 60 Hz as appropriate.
The line speed display is linearly proportional to the output frequency 0 to 50Hz or 0-60 Hz as