4-43
03- 07 Up/Down Keep Frequency Status after Stop Command
Range
【0】: After a stop command in Up/Down mode, the preset frequency is held as the
inverter stops,and the UP/Down function is disabled.
【1】After a stop command in Up/Down mod, the preset frequency is reset to 0 Hz
as the inverter stops.
【2】: After a stop command in Up/Down mode,, the preset frequency is held as the
inverter stops, and the UP/Down function remains enabled.
03 - 07 = 【0】, When run signal is removed (Stop Command), the output frequency is stored in
parameter 05-01( Key pad Frequency).
03 - 07 =【0】In stop mode since frequency can not be increased or decreased from Up/Down
terminals then keypad can be used to change the frequency by modifying parameter 05-01.
Set 03 - 07 = 【1】, In Up/down frequency mode inverter will ramp up from 0Hz on Run command and
Ramp down to 0 Hz on stop command.
03- 08 Multifunction terminals S1~S6 scan time
Range
【1~200】2ms
Multifunction input terminal On/Off periods will be scanned for the number of cycles according to the set
value in parameter 03-08. If the signal status for ON or OFF period is less than the set period it will be
treated as noise.
Scan period unit is 2ms.
Use this parameter if unstable input signal is expected, however setting long scan time periods results in
slower response times.
※
Note: Terminal SF is for safety switch, SF can cut off the inverter voltage output.
03- 09 S1~S5 Input Type Selection NO & NC
Range
【xxxx0】:S1 NO 【xxxx1】:S1 NC
【xxx0x】:S2 NO 【xxx1x】:S2 NC
【xx0xx】:S3 NO 【xx1xx】:S3 NC
【x0xxx】:S4 NO 【x1xxx】:S4 NC
【0xxxx】:S5 NO 【1xxxx】:S5 NC
03- 10 S6 Input Type Selection NO & NC
Range
【xxxx0】:S6 NO 【xxxx1】:S6 NC
“NO”: Normally open, “NC”: Normallly closed. . Select as required
For selecting Normally Open (NO) or Normally Closed (NC) set the relevant digit in parameter
03-09/03-10 to 0 or 1 as required.
In order to enable parameters 03-09/03-10, please set 03-20 = 1 (internal control) beforehand.
Set Parameter 03-09 first before you use the Parameters 00-02/00-03=1 to set the inverter run
mode to External multifunction inputs.
For example, to select S1,S2 as NC, while S3,S4,S5 as NO, set 03-09 = 00011
03-11 Multifunction Output Relay RY 1 functions. ( Terminals R1C,R1B, R1A )
03-12 Multifunction Output Relay RY 2 functions. ( Terminals R2B, R2A )
Range
【0】:Run
【1】:Fault
【2】:Output Frequency Reached
【3】:Output Frequency Reached within Preset Range (3-13±3-14)
【4】:Output Frequency Detection 1 (> 03-13)
【5】:Output Frequency Detection 2 (< 03-13)
【6】:Auto-restart
【7】:Momentary AC Power Loss---------------------------------( refer to 07-00)
【8】:Rapid Stop ( Decelerate to Stop)
【9】:Base Block Stop Mode
【10】:Motor Overload Protection (OL1)
【11】:Drive Overload Protection (OL2)
【12】:Over Torque Threshold Level (OL3)
【13】:Preset Current level Reached -------------------------( refer to 03-15/03-16)
【14】:Preset Brake Frequency Reached -----(refer to 03-17/03-18)