4-69
PLC Command
Information
Inverter response
information
Master
(PLC)
Slave
(INV-E510)
Slave
(INV-E510)
Master
(PLC)
3.5 Characters 09-09 set value
10-PID function Setup
PID block diagram
10- 00 PID target value selection
Range
0:Potentiometer on Keypad
1:External AI1 Analog Signal Input
2:External AI2 Analog Signal Input
3:Target Frequency set by Communication method.
4:Set from keypad by parameter 10-02.
10-00 selections are only effective when frequency source selection is set to PID by parameters 00 -
05 / 00 - 06= 6.
10- 01
PID feedback value selection
Range
0:Potentiometer on Keypad
1:External AI1 Analog Signal Input
2:External AI2 Analog Signal Input
3:Communication setting Frequency
Note: 10-00 and 10-01 can not be set to the same value.
10- 02 PID Keypad Input
Range
0.0~100.0%
10- 03 PID Mode Selection
Range
0:PID Function disabled
1:FWD Characteristic.
Deviation is D-controlled
2:FWD Characteristic.
Feedback is D-controlled
3:REV Characteristic.
Deviation is D-controlled
4:REV Characteristic.
Feedback is D-controlled
10- 03 =1
Deviation (target/detected value) is derivative controlled in unit time set in parameter 10-07.