4-66
08- 06 Operation After Overload Protection is Activated
Range
0:Coast-to-Stop After Overload Protection is Activated
1:Drive Will Not Trip when Overload Protection is Activated (OL1)
08- 06 = 0: On overload condition the inverter coast to stop as the thermal relay detects the
overload and the display will flash OL1.To reset Press the ‘Reset’ key or use an external reset to
continue to run.
08- 06 = 1: On overload condition the inverter continues to run, display flash with OL1, until the
current falls below the overload level.
08- 07 OH Over Heat Protection
Range
0:Auto (Depends on heat sink temp.)
1:Operate while in RUN mode
2:Always Run
3:Disabled
08- 07=0: Cooling fan runs as the inverter detects temperature rise.
08- 07=1: Cooling fan runs while the inverter is running.
08- 07=2: Cooling fan runs continuously.
08- 07=3: Cooling fan is Disabled.
08- 08 AVR function
Range
0:AVR function enable
1:AVR function disable
2:AVR function disable for stop
3:AVR function disable for Deceleration
4:AVR function disabled for stop and Deceleration
5:when VDC>360/740VAVR function is disabled for stop and Deceleration
Automatic voltage regulator function provides a level of output voltage stability when there is input
voltage instability. So when
08-08=0, Input voltage fluctuations will not effect the output voltage.
08-08=1. Input voltage fluctuations will cause fluctuations on output voltage.
08-08=2. AVR is disabled during stopping to avoid an increase in stopping time.
08-08=3. AVR is disabled only during deceleration from one speed to another speed. This will avoid
longer than required deceleration time.
08-08=4 AVR function disabled for stop and deceleration.
08-08=5 When VDC>360V(200V class)or VDC>740V(400V class), AVR function is disabled for stop
and deceleration.
08- 09
Input Phase Loss Protection
Range
0:Disabled
1:Enabled
When 08-09=1:On phase loss warring message PF is displayed..
08- 10
Output phase lost protection
Range
0:Disabled
1:Enabled
When 08-10=1: On output phase loss ,warning message LF is displayed...
08- 11 Motor type selection:
Range
0:Electronic relays protect standard motor
1: Electronic relays protect inverter duty motor
08- 12 Motor Overload Protection Curve Selection:
Range
0:Constant Torque (OL =103 %) (150 % for 1 Minute)
1:Variable Torque (OL = 113 %)(123 % for 1 Minute)
When 08-11=0:Set 02-06 as the rated frequency of the motor.