07- 03 Reset Mode Setting
Range
0:Enable Reset Only when Run Command is Off
1:Enable Reset when Run Command is On or Off
07-03=0 Once the inverter is detected a fault, please turn Run switch Off and then On again to
perform reset, otherwise restarting will not be possible.
07- 04 Direct Running on Power Up
Range
0:Enable Direct Running on Power Up
1:Disable Direct Running on Power Up
07- 05 Delay-ON Timer (Seconds)
Range
1.0~300.0 Sec
When direct run on power up is selected by 07-04=0 and the inverter is set to external run by
(00-02/00-03=1), if the run switch is ON as power is applied, the inverter will auto start.
It is recommend that the power is turned off and the run switch is also off to avoid possibility of
injury to operators and damage to machines as the power is reapplied.
Note: IF this mode is required all safety measures must be considered including warning labels.
When direct run on power up is disabled by 07-04=1 and if the inverter is set to external run by
(00-02/00-03=1), if the run switch is ON as power is applied, the inverter will not auto start and the
display will flash with STP1. It will be necessary to turn OFF the run switch and then turn ON again to
start normally.
07- 06 DC Injection Brake Start Frequency (Hz)
Range
0.10 ~ 10.00Hz
07- 07 DC Injection Brake Level (%) (Current Mode)
Range
0.0~ 150.0%
07- 08 DC Injection Brake Time(Seconds)
Range
0.0 ~ 25.5Sec
07- 08 / 07- 06 set the DC injection brake duration and the brake start frequency, as shown below:
Frequency
T
07-08
07-06
RUN
Command
Run Stop
07-09 Stopping Method
Range
0: Deceleration to stop
1: Coast to stop
07- 09 = 0: After receiving stop command, the motor will decelerate to stop according to setting of
00-15, deceleration time 1.
07- 09 = 1: After receiving stop command, the motor will free-run (Coast) to stop.
07-10 Starting Methods
Range
0: Normal Start
1: Speed Search
07-10=0On starting, the inverter accelerates from 0 to target frequency in the set time.
07-10=1On starting, the inverter accelerates to target frequency from the detected speed of motor.
07-11 Starting method for auto restart after fault
Range
0: Speed Search
1: Normal Start