4-11
Group 03- External Digital Inputs and Relay Output Functions
No. Description Range
Factory
Setting
Unit Note
03-00
Multifunction Input Term. S1 0:Forward/Stop Command
0 -
03-01
Multifunction Input Term. S2
1:Reverse/Stop Command 1 -
03-02
Multifunction Input Term. S3
2:Speed Selection 1 2 -
03-03
Multifunction Input Term. S4
3:Speed Selection 2 3 -
03-04
Multifunction Input Term. S5
4:Speed Selection 3 4 -
03-05
Multifunction Input Term. S6
5:Speed Selection 4
17
6:Jog Forward Command
7:Jog Reverse Command
8:Up Command
9:Down Command
10:Acc/Dec 2
11:Acc/Dec Disabled
12:Main/Alternative run source
select
13:Main/ Alternative Frequency
Command select
14:Rapid Stop ( Decel to stop )
15:Base Block
16:Disabl PID Function
17: Fault Reset
18:Auto Run Mode Enable
19:Speed Search
20:Energy Saving (only V/F)
21:Reset PID integral value to Zero
22:Counter Input
23:Counter reset
24:PLC Input
25:Pulse Input-Width Measure (S3)
*6
26:Pulse Input-Frequenct Measure
(S3)
*6
27:Enable KEB Function
28:Fire mode function
*5
03-06
Up/Down frequency step 0.00~5.00 0.00 Hz
03-07
Up/Down Keep Frequency Status
after Stop Command
0:When Up/Down is used, the preset
frequency is held as the inverter
stops, and the UP/Down function is
disabled
0
-
1:When Up/Down is used, the preset
frequency is reset to 0 Hz as the
inverter stops.
2:When Up/Down is used, the preset
frequency is held as the inverter
stops, and the UP/Down is available.
03-08
S1~S6 scan confirmation
1~200 Number of Scan cycles 10 2ms
03-09
S1~ S5 switch type select
xxxx0:S1 NO xxxx1:S1 NC
00000 -
xxx0x:S2 NO xxx1x:S2 NC
xx0xx:S3 NO xx1xx:S3 NC
x0xxx:S4 NO x1xxx:S4 NC
0xxxx:S5 NO 1xxxx:S5 NC