4-12
Group 03- External Digital Inputs and Relay Output Functions
No. Description Range
Factory
Setting
Unit Note
03-10
S6 switch type select xxxx0:S6 NO xxxx1:S6 NC 00000 -
03-11
Output Relay RY1
( Terminals R1A,R1B, R1C )
0:Run 0
-
03-12
Output Relay RY2.
( Terminals R2A, R2B )
1:Fault
1
2:Output Frequency Reached
3:Output Frequency Reached within
Preset Range (3-13±3-14)
4:Output Frequency Detection1(>
3-13)
5:Output Frequency Detection2(<
3-13)
6:Auto Restart
7:Momentary AC Power Loss
8:Rapid Stop
9:Base Block
10:Motor Overload Protection(OL1)
11:Drive Overload Protection(OL2)
12:Over-torque Threshold Level
(OL3)
13:Preset Output Current Reached
(03-15~16)
14:Brake Control (03-17~18)
15:PID Feedback Signal Loss
16: Single pre-set count (3-22)
17: Dual pre-set count (3-22~23)
18:PLC Status Indicator (00-02)
19:PLC control
20:Zero Speed
*6
03-13
Preset Frequency Reached Level
0.00~599.00 0.00 Hz *1
03-14
Frequency Reached Detection
Range (±)
0.00~30.00 2.00 Hz *1
03-15
Preset output current reached
0.1~15.0 0.1 A
03-16
Preset output Current detection
delay Time
0.1~10.0 0.1 Sec
03-17
Brake Release
level
0.00~20.00 0.00 Hz
03-18
Brake Engage
Level
0.00~20.00 0.00 Hz
03-19
Relay Output function type
0:A (Normally open)
1:B (Normally close)
0 -
03-20
Internal / external multi-function
input terminal selection
0~63 0 -
03-21
Action to set the internal
multi-function input terminals
0~63
0 -
03-22
Pre-set count 1
0~9999
0 -
03-23
Pre-set count 2
0~9999
0 -
03-24
Output under current detection
0:Disable
0 -
1:Enable
03-25
Output under current detection
level
5%~100%
20% %
03-26
Output under current detection
delay time
0.0~50.0s
20.0 Sec