4.4 Specification Description on Built-in PLC Function
PLC programs can be developed on PC (Windows base software) or PDA (WinCE base software)
for download to E510.
E510 Inputs and outputs can be set for PLC functionality. Speed functions can be set using the
built-in PLC functionality. .
PLC function is selected by setting inverter Run mode by parameter (00-00=3). Inputs can be set
by parameters 03-00~03-05 = 24 (PLC Application).
4.4.1 Basic Instruction Set
P
NO / NC
Input Instruction
I i
I1I6 / i1i6
Output Instruction
Q Q Q Q Q q
Q1Q2 / q1q2
Auxiliary Instruction
M M M M M m
M1MF / m1mF
Special Register
V1~V7
Counter Instruction
C C c C1~C8 / c1~c8
Timer Instruction
T T t
T1T8 / t1t8
Analog Comparing
Instruction
G G g
G1G8 / g1g8
Encoder Comparing
Instruction
F F f F1~F8 / f1~f8
ADD-DEC Instruction
AS AS1~4
Mul-DIV Instruction
MD MD1~4
Description for Special Register
V1: Setting Frequency Range: 0.1~599.0Hz
V2: Operation Frequency Range: 0.1~599.0Hz
V3: AI1 Input Value Range: 0~1000
V4: AI2 Input Value Range: 0~1000
V5: Keypad VR Input Value Range: 0~1000
V6: Operation Current Range: 0.1~999.9A
V7: Torque Value Range: 0.1~200.0%
Upper differential Lower differential
Other
Instruction
Symbol
Differential Instruction
D d
SET Instruction
RESET Instruction
P Instruction
P
Open circuit (On status)
“ “
Short circuit (Off status)
“--”
Connection symbol Description
Connecting left and right Components
Connecting left, right and upper Components
Connecting left, right, upper and lower Components
Connecting left, right and lower Components