4-49 
 
03- 22  Pre-set count 1 
Range 
【0~9999】 
03- 23  Pre-set count 2 
Range 
【0~9999】 
 
  The internal counter function can be used to count external pulses and activate RY1 & RY2 output 
relays to indicate the pre-set counts reached set in parameters 03-22 & 03-23. 
  Internal counter counts can be checked against a single pre-set value or a dual pre-set value. 
 For single pre-set count, set parameter 03-22 to the required pre-set count.   
 
To activate relays RY1 or RY2 for a single pre-set count set parameter 03-11 (RY1) or 03-12 (RY2) 
as required to 16. 
 
Pulse inputs at the selected terminal will increment the internal counter until the pre-set count in 
parameter 03-22 is reached then the selected Ry1 or Ry2 relay will be turned ON. 
Removing the input signal when the pre-set count is reached the counter is reset to zero and the 
selected relay will be turned off. 
 
 For Dual pre-set count, set 03-23 to turn ON the selected relay and Set parameter 03-22 to turn 
off the selected Relay.     
 
To activate relays RY1 or RY2 for a Dual pre-set count set parameter 03-11 (RY1) or 03-12 (RY2) 
as required to 17. 
 
Pulse inputs at the selected terminal will increment the internal counter until the pre-set count in 
parameter 03-23 is reached then the selected Ry1 or Ry2 relay will be turned ON. Then as the 
pulse input is continued, the counts will be incremented until the pre-set count set in parameter 
03-22 is reached as soon as the input pulse is removed the counter is rest to zero and the selected 
Relay is turned off. 
 
03-22 pre-set value must be ≥ pre-set value of 03-23 
 
  Example diagram for single&dual preset counts using RY1&RY2 
Count display 
set by 
parameter
12-00=00008
Dual preset-count set by parameter 03-
11=17 (RY1) and 03-22=4 , 03-23=2
Single preset-count set by parameter 
03-12=16 (RY2) 03-22=4 
The width of the trigger 
signal should be large 
than 2ms
C0001 C0002 C0003 C0004
C0001
C0002
C0000
C0003