4-23
Group 11- Performance Control Functions
No. Description Range
Factory
Setting
unit Note
11-00
Reverse Operation Control
0: Reverse Command is Enabled
1: Reverse Command is Disabled
0 -
11-01
Carrier Frequency (kHz) 1~16 5 KHz
11-02
Carrier Mode Selection
0: Mode0, 3Phase PWM modulation
1: Mode1, 2Phase PWM modulation
2: Mode2, 2Phase Soft PWM Modulation
0 -
11-03
Carrier Frequency
Reduction by Temperature
Rise
0:Disable
1:Enable
0 -
11-04
S-Curve Acc 1 0.0 ~ 4.0 0.2 Sec
11-05
S-Curve Acc 2 0.0 ~ 4.0 0.2
Sec
11-06
S-Curve Dec 3 0.0 ~ 4.0 0.2
Sec
11-07
S-Curve Dec 4 0.0 ~ 4.0 0.2
Sec
11-08
Skip Frequency 1
0.00 ~ 599.00
0.00 Hz *1
11-09
Skip Frequency 2
0.00 ~ 599.00
0.00 Hz *1
11-10
Skip Frequency 3
0.00 ~ 599.00
0.00 Hz *1
11-11
Skip Frequency Range
Bandwith (±)
0.00 ~ 30.00 0.00 Hz *1
11-12
Energy Saving Gain (V/F
Mode)
0 ~ 100 80 %
11-13
Regeneration Prevention
Function
0:Disable
0
-
1:Enable
2:Enable (only during constant speed)
11-14
Regeneration Prevention
Voltage Level
200V:300.0~400.0 380.0
V
400V:600.0~800.0 760.0
11-15
Regeneration Prevention
Frequency Limit
0.00 ~ 15.00
3.00 Hz
11-16
Regeneration Prevention
Voltage Gain
0~200 100 %
11-17
Regeneration Prevention
Frequency Gain
0~200 100 %