4-23
Group 11- Performance Control Functions
No. Description Range
Factory
Setting
unit Note
11-00
Reverse Operation Control
0: Reverse Command is Enabled
1: Reverse Command is Disabled
0 -
11-01
Carrier Frequency (kHz) 1~16 5 KHz
11-02
Carrier Mode Selection
0: Mode0, 3Phase PWM modulation
1: Mode1, 2Phase PWM modulation
2: Mode2, 2Phase Soft PWM Modulation
0 -
11-03
Carrier Frequency
Reduction by Temperature
Rise
0:Disable
1:Enable
0 -
11-04
S-Curve Acc 1 0.0 ~ 4.0 0.2 Sec
11-05
S-Curve Acc 2 0.0 ~ 4.0 0.2
Sec