4-68
08- 18 Ground Fault Detection
Range
0: Disable
1: Enable
ON dectection of Ground fault if 08-18 = 1, fault message (GF) will be displayed..
* Note: this function is only available for inverter Frames 3, 4.
09- Communication function setup
09- 00 Assigned Communication Station Number
Range
1 ~ 32
09-00 to sets the communication station number when there is more that one unit on the
communication network. Up to 32 Slave units can be controlled from one master controller such as a
PLC.
09- 01 RTU code /ASCII code Selection
Range
0:RTU
1:ASCII
09- 02 Baud Rate Setting (bps)
Range
0:4800
1:9600
2:19200
3:38400
09- 03 Stop Bit Selection
Range
0:1 stop bit
1:2 stop bits
09- 04 Parity Selection
Range
0:No Parity
1:Even Parity
2:Odd Parity
09- 05 Data Format Selection
Range
0:8 bit data
1:7 bit data
Set 09-01~09-05 to configure communication format before starting communication.
RTU can only used for 8 bits
09- 06 Communication time-out detection time
Range
0.0~25.5s
09- 07 Communication time-out operation selection
Range
0:Stop in deceleration time 1 and show COT after communication timeout
1:Stop in free run mode and show COT after communication timeout
2:Stop in deceleration time 2 and show COT after communication timeout
3:Keep running and show COT after communication timeout
Time-out detection time: 00.0~25.5sec; setting 00.0 sec: disable time-out function.
09- 08 Comm. fault tolerance count.
Range
1~20
When number of communication errors 09-08 settingkeypad display shows ERR6.
09- 09 Wait time of inverter transmission
Range
5~65ms
Sets the inverter response delay time. This is the time between the controller message and the start of the
inverter response message. Refer to figure. Set the controller receive time-out to a greater value than the
wait time parameter (09-09).