4-46
03-15 Preset output current reached
Range
【0.1~15.0】 A
03-16 Preset output Current detection delay Time
Range
【0.1~10.0】 Sec
03-11=【13】RY1 will be on as soon as the output current value > preset current setting (03-15).
03-15: Setting range (0.1~15.0 Amps ) as required according to the rated motor current.
03-16: Setting range (0.1~10.0) unit: seconds
03-16
Fixed
Value
100msec
03-15
03-11
ON
I load
100%
T
03-17
Brake Release Level
Range
【0.00~20.00】 Hz
03-18
Brake Engage Level
Range
【0.00~20.00】 Hz
If 03-11 =【14】
In accelerating mode. RY will be ON as soon as the actual output frequency reaches the external
Brake release level set in parameter 03-17.
In decelerating mode, RY will be OFF as soon as the actual output frequency reaches the external
Brake engage level set in parameter 03-18.
Timing diagram for 03-17 ≤ 03-18 is shown below:
03-17
03-18
03-11=14
RUN
command
Hz
T
ON OFF
RUN STOP
Timing diagram for 03-17
≥ 03-18 is shown below:
RY output