Group 07- Start/Stop Command Setup
No. Description Range
Factory
Setting
Unit Note
07-00
Momentary Power Loss
and Restart
0: Momentary Power Loss and Restart Disable
1: Momentary Power Loss and Restart Enable
0 -
07-01
Auto Restart Delay
Time
0.0~800.0 0.0 Sec
07-02
Number of Auto Restart
Attempts
0~10 0 -
07-03
Reset Mode Setting
0: Enable Reset Only when Run Command is Off
1: Enable Reset when Run Command is On or
Off
0 -
07-04
Direct Running on
Power Up
0: Enable Direct run on power up
1: Disable Direct run on power up
1 -
07-05
Delay-ON Timer 1.0~300.0 1.0 Sec
07-06
DC Injection Brake Start
Frequency
0.10 ~ 10.00 1.5 Hz
07-07
DC Injection Brake
Level (Current Mode)
0.0 ~ 150.0 50.0 %
07-08
DC Injection Brake
Time
0.0 ~ 25.5 0.5 Sec
07-09
Stopping Method
0: Deceleration to stop
1: Coast to stop
0 -
07-10
Starting Methods 0: Normal Start 1: Speed Search 0 -
07-11
Starting method for auto
restart after fault
0: Speed Search 1: Normal start 0 -
07-12
Power Loss Ride
Through Time
0.0 ~ 2.0 0.5 Sec
07-13
Main Circuit Low
Voltage Detection Level
150.0~210.0 300.0~420.0
190.0/3
80.0
Vac
07-14
Kinetic Energy Back-up
Deceleration Time
0.0~25.0: KEB Deceleration Time 0.0 Sec
07-15
DC Injection Brake
Mode
0 : Current Mode 1 : Voltage Mode
1 - *6
07-16
DC Injection Brake
Level (Voltage Mode)
0.0~10.0 4.0 % *6