4-77
Range ----
12- 15 Frequency command when fault appeared
Range ----
In addition to the main circuit capacitors above, the theoretical value of life diagnosis are only for
reference.
13 Inspection & Maintenance Functions
13- 00 Drive Horsepower Code
Range
----
Inverter Model:
13- 00 show
Inverter Model:
13- 00 show
E510-2P5-XXX 2P5 E510- 401-XXX 401
E510-201-XXX 201 E510- 402-XXX 402
E510-202-XXX 202 E510- 403-XXX 403
E510-203-XXX 203 E510- 405-XXX 405
E510-205-XXX 205 E510- 408-XXX 408
E510-208-XXX 208 E510- 410-XXX 410
E510-210-XXX 210 E510- 415-XXX 415
E510-215-XXX 215 E510- 420-XXX 420
E510-220-XXX 220 E510- 425-XXX 425
13- 01 Software Version
Range
----
13- 02
Fault Log Display(Latest 3 faults)
Range ----
Last three faults are stored in a stack and whenever there is a new fault the previous faults are
pushed down the stack. So the fault stored in 2.xxx will be transferred to 3.xxx, and the one in 1.xxx to
2.xxx. The recent fault will be stored in the empty register 1.xxx.
Use Up▲and Down▼ keys to scroll between the fault registers.
Pressing reset key when parameter 13-02 is displayed then all three fault registers will be cleared and
the display for each register will change to 1. ---, 2. ---, 3. ---.
E.g. fault log content is ‘1.OC-C’; this indicates the latest fault is OC-C, etc.
13- 03 Accumulated Inverter Operation Time 1
Range
【0~23】Hours
13- 04 Accumulated Inverter Operation Time 2
Range
【0~65535】Days
13- 05 Accumulated Inverter Operation Time Mode
Range
【0】:Power on time
【1】:Operation time
When the operation time recorded in accumulator 1( Parameter 13-03) reaches 24 hours
The recorded value in accumulator 2 parameter 13-04 changes to 1 day and the value in
accumulator 1 is reset to 0000.
13- 06 Parameter Lock
Range
【0】:Enable all Functions
【1】:Preset speeds 05- 01~05- 15 cannot be changed
【2】:All Functions cannot be changed Except 05- 01~05- 16
【3】:Disable All Function Except 13-06
When the 13-07=00000 (not set a password), you can adjust the parameters 05-01~ 05-016 from
13-06.