3-22
3.2.3 De-rating curves
Curves below show the applicable output current de-rate due to setting of carrier frequency and the ambient
operating temperatures of 40 and 50 degrees C .
Frame1/2/3/4
(Single phase: 200V: 0.5~3HP; Single /Three phase: 200V: 0.5~3HP;
Three phase: 200V: 2~20HP 400V: 1~25HP)
100%
70%
85%
90%
50%
60%
2 4 6 8 10 12 14 16
Rating Current(In)
Carrier Frequency(KHz)
Note:
De-rate curve for ambient temperature of 50 degree C.
De-rate curve for ambient temperature of 40 degree C.
3.2.4 Capacitor reforming Guide after long storage
For correct performance of this product after long storage before use it is important that Inverter Capacitors
are reformed according to the guide below:
• 1 to 2 years storage: Apply 100% rated voltage for one hour.
• 2 to 3 years storage: Apply 25%, 50 % , 75% and 100% at 30 minutes intervals.