App3-5
4 Inverter Control
4.1 Command Data (Readable and Writable)
Register No.
Bit
Content
2500H
Reserved
2501H
Operation Signal
0
Operation Command 1 : Run 0 : Stop
1
Reverse Command 1 : Reverse 0 : Forward
2
Abnormal 1 : EFO
3
Fault Reset 1 : Reset
4
Jog Forward Command 1 : Jog Forward
5
Jog Reverse Command 1 : Jog Reverse
6
Multi-function CommandS1 1 :“ON” 0:“OFF”
7 Multi-function CommandS2 1 :“ON” 0:“OFF”
8 Multi-function CommandS3 1 :“ON” 0:“OFF”
9 Multi-function CommandS4 1 :“ON” 0:“OFF”
A Multi-function CommandS5 1 :“ON” 0:“OFF”
B
Multi-function CommandS6 1 :“ON” 0:“OFF”
C Relay R1 1 :ON 0:OFF
D Relay R2 1 :ON 0:OFF
E~F Reserved
2502H
Frequency Command
2503H write PLC password / unlock PLC password
2504H proofread password when read/write PLC
2505H
read/write ten thousand digit of parameter 12-00 (note: address of
0C00H is the read/write for 12-00 ”fourth digit to first digit”)
2506~251FH Reserved
Note: Write in zero for Not used BIT, do not write in data for the reserved register.
4.2 Monitor Data (Only for reading)
Register No. Bit Content
2520H
0
Operation state 1 : Run 0 : Stop
1
Direction state 1 : Reverse 0 : Forward
2
Inverter operation prepare state 1:ready 0 : unready
3
Abnormal 1 : Abnormal
4
DATA setting error 1 : Error
5-F
Reserved