EasyManua.ls Logo

TECO e510 series - Page 126

TECO e510 series
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-52
AI1.Analog Voltage input scaling examples by adjusting Gain, Bias & Slope parameters (04-02~04-05)
(1) Positive Bias type (04-04= 0) and effects of modifying Bias amount by parameter 04-03 and Slope type
with parameter 04-05 are shown in Fig 1&2.
Figure1: Figure2:
04- 02 04- 03 04- 04 04- 05
04- 02 04- 03 04- 04 04- 05
A 100% 50% 0 0 C 100% 50% 0 1
B 100% 0% 0 0 D 100% 0% 0 1
60Hz
30Hz
0Hz
0V 5V 10V
Hz
V
04-03
Bias
100%
50%
0%
Upper
Frequency
A
B
60Hz
30Hz
0Hz
0V 5V 10V
Hz
V
100%
50%
0%
C
D
04-03
Bias
(2)Negative Bias type and effects of modifying Bias amount by parameter 04-03 and Slope type with
parameter 04-05 are shown in Fig 3&4.
Figure3: Figure4:
04- 02 04- 03 04- 04 04- 05
04- 02 04- 03 04- 04 04- 05
E 100% 20% 1 0 F 100% 50% 1 1
60Hz
30Hz
0Hz
2V 5V 10V
Hz
V
04-03
Bias
-100%
-50%
-0%
E
Upper
Frequency
60Hz
30Hz
0Hz
5V 10V
Hz
V
04-03
Bias
-100%
-50%
-0%
F
Upper
Frequency