EasyManua.ls Logo

TECO e510 series - Page 131

TECO e510 series
222 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-57
When 05- 00 =0, Accel /Decel 1 or 2 set by parameters 00-14/00-15 or 00-16/00-17 apply to all
speeds.
When 05- 00 =1, When 05- 00 =1Individual Accel/Decel apply to each preset speed 0-15.
Parameters 05-17 to 05-48.
Formula for calculating acceleration and deceleration time:
Actual Acc time=
Time of Accel1 or 2 x Preset Frequency
Base frequency
Actual Dec time=
Time of Accel1 or 2 x Preset Frequency
Base frequency
Base frequency = parameter 01-02 when programmable V/F is selected by 01- 00=18
Base frequency = 50.00 hz or 60.00 hz when preset V/F patterns are selected
by 01- 0018
Example01- 0018,01- 02=50hz, 05- 02=10hz(preset speed1),
05-19=5s(Acc-time),05-20=20s(Dec-time)
Preset speed 1 Actual Acc time =
05 19 10( )
1( )
01 02
Hz
s

()
Preset speed 1 Actual Dec time =
05 20 10( )
4( )
01 02
Hz
s

()
Multi speed run/stop cycles with Individual accel/decel times. 05-00=1
Two modes are shown below:-
Mode1 = On/Off run command
Mode2= Continuous run command
Mode1 Example:
00- 02=1(External Run/Stop Control).
00- 04=1(Operation ModeRun/stop-forward/reverse).
S1: 03- 00=0(RUN/STOP )
S2: 03- 01=0(Forward/Reserve)
S3: 03- 02=2(Preset speed 1)
S4: 03- 03=3(Preset speed 2);
abcdef
RUN RUN RUN
ON
ON
STOP STOP STOP
OFF
OFF
RUN
command
S2
S3
S4
05-01
05-02
05-03
……
Preset
speed0
Preset
speed1
Preset
speed2
Hz
T
FWD
OFF
When the run command is On/Off, acceleration and deceleration times for each cycle can be calculated as
below:- time unit is in seconds.