Page 11-4 Document Ref 905675-001 Rev 2
Inspection Functions WWC T1 Set Up & Maintenance Manual
11.7 Release Management
Release a dispenser for the next filling:-
0 = Release via system only - no manual release possible
1 = Release via system and Infra Red Remote Control
* push on button 9 to release right side (side A)
* push on button 7 to release left side (side B)
2 = Release via system and button on the dispenser
3 to 9 = Reserved for future implementations.
11.8 Maximum Time for a Filling
Set the maximum time the pump motor can be active (starts when the nozzle is lifted):-
0000 = Function disabled
5959 = Max time (59 minutes and 59 seconds)
1500 = Default value (Except GB default = 1000)
Note : The application has priority. If the maximum delivery timer is set in the application
then this is the default and it is not possible to increase this value in this menu (although
it can be decreased)..
11.9 Time Between Two Fillings
Set the minimum time to elapse between two successive fillings:-
0000 = Function disabled (default)
0959 = Max time (9 minutes and 59 seconds)
11.10 Maximum Time of No Flow
Within this set time, the flow must start and pulses must be detected. If no flow is detected
during this time, the pump motor is switched off. The pump motor is also switched off
during delivery when the flow is stopped for this length of time. The delivery data will
become available once the nozzle is replaced. Set the time limit:-
0000 = Function disabled
0959 = Max time (9 minutes and 59 seconds)
0100 = Default value (1 minute)