Page 6-16 Document Ref 905675-001 Rev 2
Maintenance Modes WWC T1 Set Up & Maintenance Manual
Issue B
6.16 Stop/Off Switch
This function allows the back-up battery to be switched off to enable Maintenance to be
carried out in the event of a power failure. It is only available with kernel versions <=01.08.
6.17 Fuel Leak Detection
At the start of each delivery, a leak test is started via a request from the kiosk. Up to three
attempts are made to verify the leak. If the leak is verified, the results of the leak tests are
forwarded to the kiosk via special messages.
Display Explanations/comments
S t o P Stop/Switch Off menu.
Press 9 to toggle between yes (enable) and no (disable).
no
Press 7 to save and continue.
Display Explanations/comments
F L E A Fuel Leak menu.
v0
Note : This menu is only available with selected configurations.
t1
Set volume (0 to 99 cl):-
v 0 is flashing. Press 9 to increase this value.
Press 8 to save and continue.
F L E A Set time (0 to 2 seconds):-
v0 t 0 is flashing. Press 9 to increase this value.
t0
Note : 20 = 2 seconds.
Press 7 to save and continue.
F L E A If v and t have assigned values (i.e. not 0) then the type of leak
n0
test (n) can be set (range 0 to 3).
Press 9 to change the value of n to:-
0 = never execute leak test
1 = execute leak test after request from kiosk
2 = execute leak test in stand-alone mode only
3 = always execute leak test
Press 7 to save and continue.