Page 6-26 Document Ref 905675-001 Rev 2
Maintenance Modes WWC T1 Set Up & Maintenance Manual
Issue B
6.28 Valve Reponse Value
The parameter specifies the volume to be taken, after a close valves command, before the
fuel flow rate changes. This function is used to determine when the delivery speed should
change i.e. For preset valves, it determines when the normal flow valve closes and fuel
flow rate is switched to low flow.
Note : The default values may differ according to the kernel version.
6.27 Optional Preset Valve
This function allows the use of a low flow valve (reduction valve) in parallel with the
normal flow valve (stop valve) so that during a delivery, both valves are opened. It is
designed to support the use of different preset valve mechanisms.
Display Explanations/comments
dEL I v Preset Valve menu.
PrST v Press 9 to toggle between off (disable) and on (enable).
oFF
Press 7 to save and continue.
Display Explanations/comments
v A L v E Valve Response menu.
r E S P L Set the Low value (for single meter nozzles):-
10
Default 10 is flashing. Press 9 to increase the value (in 5cl
increments up to max. 95cl).
Press 7 to save and continue.
v A L v E Set the High value (for two meter nozzles):-
rESPH Default 20 is flashing. Press 9 to increase the value (in 5cl
20
increments up to max. 95cl).
Press 7 to save and continue.