Page 2-14 Document Ref 905675-001 Rev 2
Product Information WWC T1 Set Up & Maintenance Manual
Issue A
Parameters:-
•function is disabled 0000
•max. time 0959 (= 9 minutes and 59 seconds)
•default value 0100 (certain applications may overrule this)
Time Between Two Fillings Menu (Inter delivery time out)
This is the minimum time to elapse between two successive fillings.
Parameters:-
•function is disabled 0000
•max. time 0959 (= 9 minutes and 59 seconds)
•default value disabled 0000 (certain applications may overrule this
e.g. Dunclare : fixed at 5 seconds)
Maximum Time of No Flow Menu
This is the maximum period allowed between powering the pump motor and the
detection of fuel flow. If no flow is detected, the pump motor switches off.
Parameters:-
•deliveries are disabled 0000
•max. time 0959 (= 9 minutes and 59 seconds)
•default value 0100 (certain applications may overrule this)
Delivery Mode
The calculator must totalise the amount, volume and number of fillings according
to the delivery mode selected. The delivery mode is set as follows:-
• Standalone 0
•Console cash 1
Product Position
This defines the position of the Electromechanical Totalisers (EMT), the Unit
Price Displays (UPD) and the Product Lights per product and per side. It is not
possible to select another UPD position for product 1 other than the appropriate
EMT.
For programming information, refer to section 6.xx
•Product 1 to 5 - position 1
- position 2
- position 3
- position 4
- position 5
Note: This menu has been removed from the Option Controller Board (OCB)
menu because the EMTs are not controlled via the OCB. The UPD and
Product Lights are controlled via the OCB.