Comm5 UCMs
BMTW-SVN01F-EN 145
Figure 65. Communication Stubs used with a Repeater
Figure Note:
Maximum wire length on either side of the repeater is 4,500 ft (1,400 m).
The link repeater is limited to 60 devices on either side of the link.
*Termination resistors placed at the end of each link. The resistance value of
the termination resistor is 105-ohm resistor for Level 4 wire at each end of the
link. For Trane “purple” wire use an 82-ohm resistor at each end of the link.
Repeater
C
o
m
m
s
t
u
b
C
o
m
m
s
t
u
b