Component
Maintenance Period
Monthly By
User
Every
3Months
Every
6Months
Annually
Refrigerating Circuit
Check compressor noise/vibrations X
Check oil level through compressor sight glass X
Adjust/tighten compressor/functional
elements
X
Check sight glass for problem detection X
Check starting/running amps X
Check refrigerating circuit main pressures X
Check compressor suction superheat X
Check discharge temperature X
Check subcooling X
Air Cooled
Condenser/Drycooler
(if applicable)
Check fan bearings X
Check fan motor mounts for tightness X
Check coil condition X
Check pipeline supports X
Check fan speed controller operation X
Water/Glycol Pump See manual for the pump