2.6 Component TechnicalSpecifications
2.6.1 IT rackcabinet
The Vertiv™ SmartRow™ 2 IT rack cabinet (MSR2) conforms to the industry-standard (EIA-310-E) 19-inch cabinet hardware
devices, which includes servers, voice, data, internet network equipment, and more for indoor environments, such as data
centers or rooms.
Parameter / Component Specification (Per Cabinet)
Dimensions (width x height x depth)
600 mm x 2000 mm x 1400 mm
(23.6 x 55.1 in x 78.7 in)
Lock Intelligent lock
Load 1300 kg (2866 lbs)
User space 42U
Maximum installation depth 734 mm (28.9 in)
Smart lighting
Front door: three-color lights
Rear door: white light
Transportation ISTA 3B
Table 2.11 IT Cabinet Configuration Specifications
2.6.2 Thermal management system
The thermal management system includes variable frequency precision air conditioning and emergency ventilation systems,
as shown in the figures in System Appearance and Components on page4 .
The emergency ventilation system is available for indoor environments such as data centers and rooms. When the cabinet is
hot, the system turns on automatically to combat the rising temperature of the enclosed space and to allow maintenance
personnel more time for troubleshooting.
Parameter / Component
Specification
CRD10 CR019
Dimensions, W x H x D, in. (mm.) 11.8 x 78.7 x 56.7 (300 x 2000 x 1440) 11.8 x 78.7 x 56.7 (300 x 2000 x 1440)
Load dry, lbs. (kg.) 1232.4 (559) 1228 (557)
Cooling power (kW) 10 20
Nominal airflow (CFM) 1960 2250
Plenum lock Intelligent/one point
2.6.3 Power distribution system
The power distribution system includes a PDU module that is powered by either a Vertiv™ Liebert® GXT5 UPS 10kVA or a
Vertiv™ Liebert® GXT5 UPS 20kVA. The 20kVAUPS contains internal batter modules. In the PMC10, the PD is mounted to the
10kVAUPS. In the PMC20, the 20kVA uses an external VMBC and a rack PDU extender for the power connection.
NOTE: The 10kVA UPS uses an internal MBC, whereas the 20kVA UPS uses an external VMBC.