3 Site Planning
3.1 System Layouts
Note the following information about system layouts:
• The environmental conditions of the system should be indoors with temperatures ranging from 32 °Fto 104 °F (0
°C to 40 °C).
• The floor must be level and continuous with no breaks disrupting the surface. For example, expansions joints and
raised floor tile gaps should be sealed, no floor drains should be present, and so on.
• Ensure there are no water sprinkler heads within 0.5 m of the system.
• Install the system in accordance with national and electrical codes.
The following tables detail the system and component dimensions, as well as the rack, cooling, and power capacity of each
configuration.
Configuration
Number
SKU
Row
Dimensions,
(L x H x D) in.
(mm.)
1
Row
Weight,
lbs. (kg.)
Minimum
Staging
Area, ft
2
(m
2
)
Rack
Type, U
x in. x in.
(mm. x
mm.)
Main Input
Breaker
Size
2
Condenser
Breaker Size
Condenser
Dry Weight,
lbs. (kg.)
1 SR2N02010NAA1
82.7 x 107 x 55.2
(2100 x 2249 x
1400)
4651.8
(2110)
116.8 (10.85)
42U x 23.6
x 55.1
(600 x
1400)
100A N/A
3
132.3 (60)
2 SR2N02010PAA1
82.7 x 107 x 55.2
(2100 x 2249 x
1400)
4713.5
(2138)
123.1 (11.43)
42U x 23.6
x 55.1
(600 x
1400)
100A N/A
3
132.3 (60)
3 SR2N02010FAA1
94.5 x 107 x 55.2
(2400 x 2249 x
1400)
6089.2
(2762)
151.9 (14.11)
42U x 23.6
x 55.1
(600 x
1400)
100A N/A
3
132.3 (60)
4 SR2N03010NAA1
106.3 x 107 x
55.2 (2700 x
2249 x 1400)
5026.5
(2288)
131.4 (12.2)
42U x 23.6
x 55.1
(600 x
1400)
100A N/A
3
132.3 (60)
5 SR2N03010PAA1
106.3 x 107 x
55.2 (2700 x
2249 x 1400)
5136.8
(2330)
137.6 (12.78)
42U x 23.6
x 55.1
(600 x
1400)
100A N/A
3
132.3 (60)
6 SR2N03010FAA1
118.2 x 107 x 55.2
(3000 x 2249 x
1400)
6512.5
(2954)
166.5 (15.46)
42U x 23.6
x 55.1
(600 x
1400)
100A N/A
3
132.3 (60)
7 SR2N03020NAA1
106.3 x 107 x
55.2 (2700 x
2249 x 1400)
6000.1
(2722)
137.6 (14.9)
42U x 23.6
x 55.1
(600 x
175A 15A 260.2 (118)
Table 3.1 System Layout - Dimensions
3 Site Planning Proprietary and Confidential ©2024 Vertiv Group Corp. 21
Vertiv™ SmartRow™ 2 Infrastructure Solution User Guide