11 Troubleshooting
This chapter details troubleshooting procedures for the SmartRow™ 2 infrastructure solution and the Vertiv™ Liebert®
RDU501 intelligent monitoring unit.
11.1 Monitoring Unit Common Issues and Solutions
For troubleshooting the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit, please refer to the following table for common
issues, causes, and solutions. If your specific issue is not addressed in the table below, refer to the Vertiv™ Liebert® RDU501
Intelligent Monitoring Unit User Manual shipped with the unit and lcoated on www.Vertiv.com.
Category Issue Possible Causes Solutions
Alarm
There are intelligent
communication failure alarms
in the monitoring unit's Alarms
- History page.
Improper cabling.
Check the cable clamp to ensure it's intact, and check if
the cable connection has been loosened.
After an alarm generates, the
notification system does not
respond properly. I'm receiving
less than three email or
SMSnotification (or none at
all).
Incorrect SMSmodule and mail server
configurations.
Verify that the notification configurations are correct.
Blocked SMS function.
Contact the operator to confirm if the SMSfunction is
blocked and possible workarounds.
Suspended telephone card. Confirm if the telephone card has been suspended.
If the above solutions do not resolve the issue, click Data & History - History Log. Check the log for
a record of failed mail delivery. If there is a record of such, then the network or mail server
communication is busy.
When the first login system
has an alarm or a new alarm
generates, no alarm sounds.
Device volume is muted. Unmute the device.
Browser prohibits sounds.
Based on your browser, refer to the appropriate setting
configurations:
Chrome: Go to Settings - Advanced -
Website Settings - Sounds. Check if
there is a current system address under
the Mute section. If so, delete it.
Internet Explorer:Go to Internet
Options - Advanced - Multimedia.
Check the box for Play sounds in web
pages, then click Apply.
Safari: Go to Preferences - Website -
Auto Play. Set the current system
address to Allow all auto play.
NOTE: Due to continuous browser development, the
above settings may change or fail.
Authorization
Despite the monitoring unit's
communication being normal,
the login page is not
appearing.
Incorrect IP address.
Confirm the IP address is correct. As the unit uses two
network cards, ensure the Ethernet cable is plugged
into the proper interface. If the address is static, refer to
the Ethernet port in the monitoring unit section for the
default IP value.
Poor connection
Open a Windows command prompt, then enter the
Table 11.1 Monitoring Unit Troubleshooting
11 Troubleshooting Proprietary and Confidential ©2024 Vertiv Group Corp. 113
Vertiv™ SmartRow™ 2 Infrastructure Solution User Guide