2.4 Configuration Specifications
The SmartRow™ 2 infrastructure solution offers 15 total system configuration options. Refer to the following table for
specifications of the typical system configurations. For more information, see Site Planning on page21 .
Parameter
Specification
1x Cooling
1x PMC
2x Racks
1x Cooling
1x PMC
3x Racks
2x
Cooling
1x PMC
2x Racks
2x
Cooling
1x PMC
3x Racks
1x Cooling
1x PMC
4x Racks
2x
Cooling
1x PMC
4x Racks
1x Cooling
1x PMC
5x Racks
2x
Cooling
1x PMC
5x Racks
Size (L x D x
H)
System
82.7 in. x 55.1
in. x 88.6 in.
(2100 mm. x
1400 mm. x
2250 mm.)
94.5 in. x 55.1
in. x 88.6 in.
(2400 mm. x
1400 mm. x
2250 mm.)
106.3 in. x
55.1 in. 88.6
in. (2700
mm. 1400
mm. x 2250
mm.)
118.1 in. x 55.1
in. x 88.6 in.
(3000 mm. x
1400 mm. x
2250 mm.)
129.9 in. x
55.1 in. x 88.6
in. (3300
mm. x 1400
mm. x 2250
mm.)
141.7 in. x
55.1 in. x
88.6. (3600
mm. x 1400
mm. 2250
mm.)
153.5 in. x
55.1 in. x 88.6
in. (3900
mm. x 1400
mm. x 2250
mm.)
165.4 in. x
55.1 in. x 88.6
in. (4200
mm. x 1400
mm. x 2250
mm.)
Air
conditioner
(with frame)
11.8 in. x 55.1 in. x 88.6 in. (300 mm. x 1400 mm. x 2250 mm.)
600 mm.
wide IT rack
cabinet
23.6 in. x 55.1 in. x 88.6 in. (600 mm. x 1400 mm. x 2250 mm.)
PMC 23.6 in. x 55.1 in. x 88.6 in. (600 mm. x 1400 mm. x 2250 mm.)
Available installation height
2
(U) (1U=44.45 mm.)
84 126 84 126 168 168 210 210
Normal cooling capacity
(kW) (return air 35 °C
(95°F), 26% humidity)
10 20
Maximum installation depth 28.9 in. (734 mm.)
Range of cooling capacity
(kW)
(30% to 100%) * maximum cooling capacity (kW)
PAC
CRD10 ACFM: 1960
CR019 ACFM: 2250
(If the configuration of multiple air-conditioning, in turn superimposed)
Color RAL7021
System environmental
conditions
Indoor, 0 °C to 40 °C.
6 Proprietary and Confidential ©2024 Vertiv Group Corp. 2 Getting Started