7 Network Settings
7.1 Vertiv™ Liebert® RDU-THD Sensors
A temperature and humidity string is installed on the front and rear doors of each cabinet in the system. The THD
(Temperature and Humidity Collector) sensor summarizes the temperature and humidity of each door. Setting the sensor
address can be done only through the dialing code.
To set the THDsensor address:
Refer to Table 7.1 below and Figure 7.1 on the next page .
NOTE: The sensor address cannot be set as 00 as it is the broadcast address.
Cabinet DIP1 - DIP4 Group Number DIP5 - DIP6 Sequence Number
PMC (factory default) 1001 9 00 0
ITrack cabinet 1 0001 1 00 0
ITrack cabinet 2 0010 2 00 0
ITrack cabinet 3 0011 3 00 0
ITrack cabinet 4 0100 4 00 0
ITrack cabinet 5 0101 5 00 0
Table 7.1 THD Sensor Address: Dial Code Settings
Group Number Sequence Number
Address
DIP 1 DIP 2 DIP 3 DIP 4 DIP 5 DIP 6
0 0 0 0 0 0 00
0 0 0 1 0 0 10
0 0 1 0 0 0 20
0 0 1 1 0 0 30
0 1 0 0 0 0 40
0 1 0 1 0 0 50
0 1 1 0 0 0 60
0 1 1 1 0 0 70
1 0 0 0 0 0 80
1 0 0 1 0 0 90
7 Network Settings Proprietary and Confidential ©2024 Vertiv Group Corp. 49
Vertiv™ SmartRow™ 2 Infrastructure Solution User Guide