Configuration
Number
SKU
Row
Dimensions,
(L x H x D) in.
(mm.)
1
Row
Weight,
lbs. (kg.)
Minimum
Staging
Area, ft
2
(m
2
)
Rack
Type, U
x in. x in.
(mm. x
mm.)
Main Input
Breaker
Size
2
Condenser
Breaker Size
Condenser
Dry Weight,
lbs. (kg.)
1400)
8 SR2N03020PAA1
106.3 x 107 x
55.2 (2700 x
2249 x 1400)
6093.6
(2764)
182.5 (16.95)
42U x 23.6
x 55.1
(600 x
1400)
175A 15A 260.2 (118)
9 SR2N03020FAA1
118.2 x 107 x 55.2
(3000 x 2249 x
1400)
7469.3
(3388)
224.6 (20.86)
42U x 23.6
x 55.1
(600 x
1400)
175A 15A 260.2 (118)
10 SR2N04020NAA1
130 x 107 x 55.2
(3300 x 2249 x
1400)
6393.4
(2900)
175 (16.25)
42U x 23.6
x 55.1
(600 x
1400)
175A 15A 260.2 (118)
11 SR2N04020PAA1
130 x 107 x 55.2
(3300 x 2249 x
1400)
6516.9
(2956)
197 (18.3)
42U x 23.6
x 55.1
(600 x
1400)
175A 15A 260.2 (118)
12 SR2N04020FAA1
141.8 x 107 x 55.2
(3600 x 2249 x
1400)
7890.3
(3579)
239.1 (22.21)
42U x 23.6
x 55.1
(600 x
1400)
175A 15A 260.2 (118)
13 SR2N05020NAA1
153.6 x 107 x 55.2
(3900 x 2249 x
1400)
6783.6
(3077)
189.5 (17.6)
42U x 23.6
x 55.1
(600 x
1400)
175A 15A 260.2 (118)
14 SR2N05020PAA1
153.6 x 107 x 55.2
(3900 x 2249 x
1400)
6937.9
(3147)
211.6 (19.65)
42U x 23.6
x 55.1
(600 x
1400)
175A 15A 260.2 (118)
15 SR2N05020FAA1
165.4 x 107 x
55.2 (4200 x
2249 x 1400)
8313.6
(3771)
253.6 (23.56)
42U x 23.6
x 55.1
(600 x
1400)
175A 15A 260.2 (118)
NOTE:
1: Does not account for the space needed for access per ADA or local codes.
2: Cable sizing: 100A = 3 AWG; 175A = 2/0 AWG
3: The 10kW condenser power is sourced from the indoor unit.
Table 3.1 System Layout - Dimensions (continued)
22 Proprietary and Confidential ©2024 Vertiv Group Corp. 3 Site Planning
Vertiv™ SmartRow™ 2 Infrastructure Solution User Guide