EasyManua.ls Logo

Vertiv SmartRow 2 - Page 29

Vertiv SmartRow 2
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
Number
SKU
ITRacks
per Row
Capacity
per Rack
(kW)
Maximum
Row
Capacity
(kW)
Cooling
Units per
Row
Redundancy
Type
PDUs
per Row
Distribution
Type
1 SR2N02010NAA1 2 5
10
1 No redundancy 2
10kW PMC
2 SR2N02010PAA1 2 5 1
Power (PDU +
UPS)
4
3 SR2N02010FAA1 2 5 2 Power + Cooling 4
4 SR2N03010NAA1 3 3.3 1 No redundancy 3
5 SR2N03010PAA1 3 3.3 1
Power (PDU +
UPS)
6
6 SR2N03010FAA1 3 3.3 2 Power + Cooling 6
7
SR2N03020NAA
1
3 6.6
20
1 No redundancy 3
20kW PMC
8 SR2N03020PAA1 3 6.6 1
Power (PDU +
UPS)
6
9 SR2N03020FAA1 3 6.6 2 Power + Cooling 6
10
SR2N04020NAA
1
4 5 1 No redundancy 4
11 SR2N04020PAA1 4 5 1
Power (PDU +
UPS)
8
12 SR2N04020FAA1 4 5 2 Power + Cooling 8
13
SR2N05020NAA
1
5 4 1 No redundancy 5
14 SR2N05020PAA1 5 4 1
Power (PDU +
UPS)
10
15 SR2N05020FAA1 5 4 2 Power + Cooling 10
Table 3.2 System Layout - Rack, Cooling, and Power Capacity
3 Site Planning Proprietary and Confidential ©2024 Vertiv Group Corp. 23
Vertiv™ SmartRow™ 2 Infrastructure Solution User Guide