Vertiv SmartRow 2 - Page 57

Vertiv SmartRow 2
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Number Name Description
1
Dual Ethernet
Ports
The dual Ethernet ports act as a two-port Ethernet switch, allowing for multiple devices to be daisy-chained.
The dual Ethernet ports can be independently configured dual Ethernet network interfaces, allowing the rPDU to
connect to two different networks.
2
Hard-Reboot
Button
Pressing the hard-reboot button reboots the IMD-03E-G module. This acts as a power cycle for the module and does
not change or remove any user information.
3
Network
Reset Button
Holding the network reset button for five seconds during normal operation will restore the default IP address and
reset the user accounts.
4 Local Display The local display shows the phase, line and circuit current values (in amperes).
5
Display
Buttons
There are three buttons near the IMD display: a back button, a forward button and a center button.
6
Remote
Sensor Port
The RJ-12 port is for connecting a Vertiv™ plug-and-play remote digital sensor (sold separately). Each digital sensor
has a unique serial number and is automatically discovered. GU2 PDUs support up to 16 sensors.
The optional Vertiv™ A2D Converter can be added to support analog sensing.
The optional SN-ADAPTER can be added to support Vertiv™ Integrated and Modular Sensors.
7 Serial Port RS-232 via RJ-45 port.
8 USB Port
The USB port provides up to 1Apower capacity for USB-connected devices to do the following:
Upload firmware
Backup/restore device configurations
Expand logging capacity via a USB storage device
Support TP-Link wireless USB adapters.
The USB port must be enabled - see USB on page 56.
Table 7.2 PDU Operation Display Panel
7 Network Settings Proprietary and Confidential ©2024 Vertiv Group Corp. 51
Vertiv™ SmartRow™ 2 Infrastructure Solution User Guide