Edge [ii] Controller Operation Manual
SECTION 6 ADVANCED SETUP
OMM-139_E 8/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 107 of 196
8. If Unit Application = Other, choose one of two Unit Other Operating Mode, either
Constant Setpt or Remote Setpt.
Unit Other Operating Mode = Constant Setpoint Unit Other Operating Mode = Remote Setpoint
Figure 6.2.6-6: Unit Application Configuration, Unit Application = Other
A. If Unit Other Operating Mode = Constant Setpt, specify the “other” setpoint in
the Unit Other Setpoint parameter. (Range: 70°F to 180°F)
B. If Unit Other Operating Mode = Remote Setpt, the following additional
parameters appear:
Analog Input Source: Select the source for the Analog Input: Spare Analog
In 1, Spare Analog In 2, Spare Analog In 3.
Name: Choose a name to associate with the analog input:
o Not Assigned
o Swing V1 Fdbk
o Blr VSP Fdbk
o SmartPlate VP
o Remote Setpt 2
o Swing V2 Fdbk
o DHW VSP Fdbk
o NOx
NOTE:
The Analog Input Source and Name parameters also appear in Step 7b, above, and in
Section 6.5.4: Analog Inputs. Changing them in any one changes them in the others.
Unit Other Remote Signal: Choose the source of the signal:
o 4-20mA/1-5V
o 0-20mA/0-5V
o Network
o BAS
Figure 6.2.6-7: Unit: Application Configuration, Unit Other Remote Signal = Network