8. If Unit Application = Other, choose one of two Unit Other Operating Mode, either
Constant Setpt or Remote Setpt.
Unit Other Operating Mode = Constant Setpoint Unit Other Operating Mode = Remote Setpoint
Figure 6.2.6-6: Unit Application Configuration, Unit Application = Other
A. If Unit Other Operating Mode = Constant Setpt, specify the “other” setpoint in
the Unit Other Setpoint parameter. (Range: 70°F to 180°F)
B. If Unit Other Operating Mode = Remote Setpt, the following additional
parameters appear:
• Analog Input Source: Select the source for the Analog Input: Spare Analog
In 1, Spare Analog In 2, Spare Analog In 3.
• Name: Choose a name to associate with the analog input:
NOTE:
The Analog Input Source and Name parameters also appear in Step 7b, above, and in
Section 6.5.4: Analog Inputs. Changing them in any one changes them in the others.
• Unit Other Remote Signal: Choose the source of the signal: