EasyManua.ls Logo

Watts AERCO Edge [ii] - Fire Control

Watts AERCO Edge [ii]
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Edge [ii] Controller Operation Manual
SECTION 6 ADVANCED SETUP
OMM-139_E 8/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 163 of 196
o Setpoint Limit Band: (If Setpoint Limiting = Enabled): Sets the number of
degrees below Setpoint High Limit the unit’s outlet temperature must fall before the
unit restarts (Default = 5°F (2.8°C), Range = 0°F to 10°F (0°C to 5.5°C))
4. The Setback Setpoint features can be used to lower the Setpoint during periods when a
lower Setpoint is appropriate, such as at night. To enable this feature, set Setback
Schedule to Enabled, then configure the following additional parameters:
Setback Setpoint: The Setpoint that will be in effect during the Setback period.
Setback Start Time: The Setback period’s start time (example: 11:00 PM). This
parameter also appears in
Setback Stop Time: The Setback period’s end time (example: 5:00 AM).
6.6.3 Fire Control
The Fire Control screen provides access to functionality that affect the firing of this unit. All four
controls apply to this unit only.
1. Go to: Main Menu Advanced Setup Performance Fire Control.
Figure 6.6.3: Performance: Fire Control
NOTE:
You can navigate from one Fire Control screen to the next in round-robin fashion using the
Page Left and Page Right icons on each screen.

Table of Contents

Related product manuals