• Upper Inlet Display: Set to Disabled if you want to hide the Inlet 2 temperature for
units with dual inlets where the upper inlet is not utilized.
• BST Return Display: Enables/ disables display of the BST Return Header sensor.
It should be enabled only when utilizing a BST return header sensor.
• Beeper: Enables/disables the audible fault alarm.
• Run Cycles/Run Hours: Displays the number of run hours/run cycles since the last
system reset. Both can be reset to 0 (or any other number).
• Reset Common Settings: To reset “common” settings and restored default
values, press Yes, then press Yes again when asked to confirm.
• Clear Fault Log: To clear the Unit Event History (see Section 7.7 Unit Event
History), press Yes, then press Yes again when asked to confirm.
• Reset All Settings: To reset all settings and restored default values, press Yes,
then press Yes again when asked to confirm.
6.2.2 Front Panel Configuration
The Front Panel Configuration screen allows you to modify the Controller’s front panel and the
touchscreen timeout setting.
Figure 6.2.2-1: Unit: Controller Front Panel – Upper Portion
1. Go to: Main Menu → Advanced Setup → Unit → Front Panel Configuration.
Figure 6.2.2-2: Unit: Front Panel Configuration Screen