Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E 8/25/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 31 of 196
2.3.2 EZ Setup: BST Manager Unit
The Manager unit will sync with all Client boilers once this process is completed. Note, if a BST
Manager setup was already performed on this or another unit, and you want to load/re-load that
setup, see Section 2.5: EZ Setup Restoring a Previous Setup.
NOTE:
All “Client” units are typically setup before starting the BST Manager setup, so their addresses
are available during this process. If they are not all setup, you will have to pause and setup all
Client units before completing the BST Manager setup.
1. Go to: Main Menu EZ Setup.
2. If the unit was previously setup, the EZ Setup screen appears showing a summary of the
previous setup (see Figure 2.3.1-1, above). You can Abort and retain the previous setup or
press Next to continue.
3. On the Select Configuration screen press BST Cascade, then press Next.
Figure 2.3.2-2: BST Manager: Select Configuration Screen
4. On the Cascade Role screen select BST Manager and then press Next. The Manager LED
will light on the front panel signifying the role of the unit.
Figure 2.3.2-3: BST Manager: Cascade Role Screen